# Modeling Liquid-Cooled Data Centers in EnergyPlus

DevFeed: [Modeling Liquid-Cooled Data Centers in EnergyPlus](<https://devfeed.tech/articles/modeling-liquid-cooled-data-centers-in-energyplus-101598.md>)

Original publisher: [Read original article](<https://arxiv.org/abs/2610.33148>)

Author: Yun-Dam Ko, Dipashreya A. Sur, Cade Napier, Carlos D. D\\'iaz-Mar\\'in, Rishee K. Jain

Published: 2026-10-27T04:00:00Z

Content type: article

Language: en

Sources: [arXiv: Distributed Computing](<https://devfeed.tech/sources/arxiv-distributed-computing.md>)

Topics: [Simulation](<https://devfeed.tech/topics/simulation.md>), [clean energy data centers](<https://devfeed.tech/topics/clean-energy-data-centers.md>)

Tags: [ai](<https://devfeed.tech/tags/ai.md>), [ai-infrastructure](<https://devfeed.tech/tags/ai-infrastructure.md>), [ai-workloads](<https://devfeed.tech/tags/ai-workloads.md>), [cooling](<https://devfeed.tech/tags/cooling.md>), [cs-ce](<https://devfeed.tech/tags/cs-ce.md>), [cs-dc](<https://devfeed.tech/tags/cs-dc.md>), [cs-lg](<https://devfeed.tech/tags/cs-lg.md>), [cs-sy](<https://devfeed.tech/tags/cs-sy.md>), [data-center](<https://devfeed.tech/tags/data-center.md>), [data-centers](<https://devfeed.tech/tags/data-centers.md>), [eess-sy](<https://devfeed.tech/tags/eess-sy.md>), [efficiency](<https://devfeed.tech/tags/efficiency.md>), [energy](<https://devfeed.tech/tags/energy.md>), [framework](<https://devfeed.tech/tags/framework.md>), [high-density](<https://devfeed.tech/tags/high-density.md>), [infrastructure](<https://devfeed.tech/tags/infrastructure.md>), [it](<https://devfeed.tech/tags/it.md>), [liquid](<https://devfeed.tech/tags/liquid.md>), [liquid-cooling](<https://devfeed.tech/tags/liquid-cooling.md>), [loops](<https://devfeed.tech/tags/loops.md>), [modeling](<https://devfeed.tech/tags/modeling.md>), [models](<https://devfeed.tech/tags/models.md>), [native](<https://devfeed.tech/tags/native.md>), [open-source](<https://devfeed.tech/tags/open-source.md>), [rack](<https://devfeed.tech/tags/rack.md>)

## AI overview

The paper introduces EnergyPlus's ElectricEquipment:ITE:LiquidCooled object to model direct-to-chip cooling across chilled-water and warm-water architectures. It links facility and rack-side water loops, coolant distribution units, and chip-junction temperatures in one solver. Comparison with an independent Modelica implementation across 21 operating conditions, including two full-year runs at one-minute resolution, reports loop-temperature RMSE no greater than 0.021 K, below the 0.1 K acceptance threshold. In the case study, warm-water cooling lowered annual PUE from 1.43 to 1.25, eliminated on-site water use, and reduced total facility energy by 37.9% versus an air-cooled baseline.

## Source excerpt

arXiv:2610.33148v1 Announce Type: cross Abstract: As AI workloads accelerate data center transition toward high-density racks with direct-to-chip (DTC) liquid cooling, existing simulation tools remain limited in evaluating whole-building and multi-year efficiency. To bridge this gap, we develop a native EnergyPlus object, ElectricEquipment:ITE:LiquidCooled, that models DTC liquid cooling for chilled-water and warm-water architectures as plant-loop components. It couples facility-water loops, rack-side secondary loops, coolant distribution units, and chip-junction temperatures within a single solver. Validation against an independent Modelica implementation across 21 operating conditions, including two full-year runs compared at one-minute resolution, yields loop-temperature RMSE at or below 0.021 K, well within the 0.1 K acceptance threshold. Our case study demonstrates that warm-water liquid cooling reduces annual PUE from 1.43 to 1.25, eliminates on-site water use, and cuts total facility energy by 37.9% relative to an air-cooled baseline. By embedding liquid-cooling logic into EnergyPlus, our work provides whole-building, long-term energy modeling for high-density AI infrastructure within an open-source framework.